Johnson Controls - TM9V060B12MP11

Below are all the different types of Johnson Controls. Select the device of your choice, to download the manual


Click here to download the manual

Contents

NOTES 1 If the furnace is equipped with NOx screens and is to be used with LP propane gas the screens must be removed prior to start up 2 Drip leg in the gas line must be installed 3 The furnace controls require correct polarity on the power supply and a proper ground 4 Y amp G must be connected to the control board for cooling operation 5 External filters are required on all configurations 6 Electrical or gas entry is available on both casing sides 7 To measure total static pressure add supply duct pressure to the return duct pressure add pressure drop across the A coil and add pressure drop across the filter Ignore negative signs on the readings 8 Inlet gas pressure should be 7 w c for natural gas and 11 w c for propan ...